L Firmware 1.37 - 09/2006 31
9400 HighLine | Parameter setting & configuration
Commissioning
Standard set-up
3.4 Standard set-up
Worksteps
Transfer application and parameter set to the controller:
1. Transfer the application preconfigured in the »Engineer« and the corresponding parameter set to the
memory module of the controller.
2. Save parameter set
. (C 57)
For a motor with an electronic nameplate (ENP):
1. Restart controller with connected motor to read out the motor data from the electronic nameplate
(ENP).
Restart the controller either by switching off and on again the voltage supply or by the device
command "Restart controller" (C00002
= "11000").
•See chapter Motor interface
Read the motor data out of the controller (C 66)
2. Save parameter set
. (C 57)
For a motor without an electronic nameplate (ENP):
Note:
Here, the motor is operated with the motor and route data detected during the initial commissioning.
In contrast to the operation of a motor with ENP no resolver errors are compensated and a uniform
saturation characteristic is considered only.
•See chapter Motor interface
Initial commissioning (C 65)
1. If required, detect rotor displacement angle. Set rotor displacement angle
(C 71)
Required for synchronous motors of an original equipment manufacturer and Lenze synchronous
motors with Stegmann absolute value encoder.
2. Save parameter set
. (C 57)