Technical data
General data and operating conditions
4
27
EDS84ASC552 EN 9.1
4 Technical data
4.1 General data and operating conditions
Conformity and approval
Conformity
CE
2006/95/EC Low-Voltage Directive
Approval
UL UL 508C Device size 1 ... 7 (0.25 ... 45 kW)
Certification of t he integrated safety system: see chapter
10.9
CSA CSA 22.2 No. 14 Device size 1 ... 7 (0.25 ... 45 kW)
Only if an external mains choke is used.
Protection of persons and device protection
Type of protection
EN 60529
IP 20 183
Specification
applies to the fully
assembled state ready
for use
does not apply to the
wire range of the
terminals
NEMA 250 Protection against accidental
contact acc. to type 1
Insulation resistance EN 61800-5-1 Overvoltage category III
Above 2000 m amsl: Overvoltage category II
Control circuit isolation EN 61800-5-1 Safe mains isolation via double / reinforced insulation for
star-point earthed mains with a rated voltage for external
conductors / star point of up to 300 V.
Short-circuit strength
Earth-fault strength
EN 61800-5-1 Motor connection: Limited, i.e. an internal protective device
responds, the controller is inhibited
(Error acknowledgement is required)
Control t erminals: Without limitation
Protective measures
against
Short circuit
Earth fault
(Earth fault strength depends on the operating status)
Overvoltage
Motor stalling
Motor overtemperature
(PTC or th ermal contact, I
2
t-monitoring)
Leakage current EN 61800-5-1 > 3.5 mA AC, > 10 mA DC Observe regulations and
safety instructions!
Mains switching Mains switching 3 times in 9 minutes (without
restrictions)
More frequent mains switching, e.g. during setting-up
operation, does not h arm the controller.
Devices of up to 22 kW are protected against overload.
A monitoring issues the ”Su03” message. The message
must be acknowledged via mains switching. Before you
switch on again: Let t he device cool down!
Devices from 30 kW are protected by the dimensioning
of the load circuit. Monitoring is not carried out.
Starting current 2xI
rated