2.12 MCTRL_MotorControl (node number 131)
9300 Servo PLC
System blocks
2−94
L
9300 Servo PLC EN 5.1
2.12.17.19 NMAX − speed monitoring (maximum speed exceeded)
This monitoring function monitors the process.
Error
Monitoring function System variable
Possible responses
No. Display TRIP Message Warning FAIL−QSP Off
x200 NMAX Maximum speed exceeded MCTRL_bNmaxFault_b
Lenze setting
Setting possible
The monitoring responds when the current speed exceeds the upper speed limit of the system or the
double value of C0011 (n
max
).
Stop!
For active loads (e. g. hoists) ensure torque−free operation of the drive. Special
system−specific measures are required!
If the actual speed value encoder fails, the monitoring may fail to respond.
The upper system speed is set under C0596:
Code LCD
Possible settings
IMPORTANT
Lenze Selection
C0596 NMAX limit
5500 Monitoring configuration: Max. speed
of the machine
0 {1 rpm} 16000