3.5.4 Causes and remedies
Fault message
Description Cause Remedy
No. Display
−−− −−− No fault
0011 OC1 Short circuit of motor cable
Short circuit Search for cause of short circuit.
Check motor cable.
Excessive capacitive charging current in the
motor cable.
Use motor cable which is shorter or of
lower capacitance.
0012 OC2 Motor cable earth fault One of the motor phases has earth contact. Search for cause of short circuit.
Check motor cable.
0015 OC5 I x t overload Frequent and too long acceleration with
overcurrent
Continuous overload with I
motor
> 1.05 x
I
rx.
Check drive dimensioning.
0016 OC6 I
2
x t overload TRIP (motor, C0120) Current overload of the motor, e.g. due to:
frequent or too long acceleration
processes
impermissible continuous current
Check drive dimensioning.
Check setting of C0120.
x018 OC8 I
2
xt overload advance warning Frequent and too long acceleration
processes with motor overcurrent.
Permanent motor overload with
I
motor
>I
rmotor
Check drive dimensioning.
1020 OU Overvoltage in DC bus Braking energy is too high.
(DC−bus voltage is higher than set in
C0173.)
Use braking unit or regenerative module.
Check dimensioning of the brake
resistance.
1030 LU Undervoltage in the DC bus DC bus voltage is lower than specified in
C0173.
Check mains voltage
Check supply cable
x032 LP1 Motor phase failure
A current−carrying motor phase has failed. Check motor.
Check motor cable.
Switch off monitoring (C0597 = 3).
The current limit value is set too low. Set higher current limit value via C0599.
0050 OH Heatsink temperature > +90 °C
Ambient temperature
T
u
> +40 °C or > +50 °C
Allow module to cool and ensure better
ventilation.
Check ambient temperature in the
control cabinet.
Heatsink is very dirty. Clean heatsink.
Wrong mounting position Change mounting position.
x053 OH3 Motor temperature
> +150 °C threshold
(temperature detection via resolver or
incremental value encoder)
Motor is thermally overloaded due to:
Impermissible continuous current
Frequent or too long acceleration
processes
Check drive dimensioning.
Switch off monitoring (C0583 = 3).
No PTC/temperature contact connected. Correct wiring.
x054 OH4 Heatsink temperature > C0122
Ambient temperature T
u
> +40 °C or
> +50 °C
Allow module to cool and ensure better
ventilation.
Check ambient temperature in the
control cabinet.
Switch off monitoring (C0582 = 3).
Heatsink is very dirty. Clean heatsink
Wrong mounting position Change mounting position.
The value specified under C0122 is set too
low.
Enter a higher value under C0122.
x057 OH7 Motor temperature > C0121
(temperature detection via resolver or
incremental value encoder)
Motor is thermally overloaded due to:
Impermissible continuous current
Frequent or too long acceleration
processes
Check drive dimensioning.
Switch off monitoring (C0584 = 3).
No PTC/temperature contact connected. Correct wiring.
The value specified under C0121 is set too
low.
Enter a higher value in C0121.
x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP