2.5 ANALOG1_IO (node number 11)
9300 Servo PLC
System blocks
2−26
L
9300 Servo PLC EN 5.1
2.5 ANALOG1_IO (node number 11)
2.5.1 Inputs_ANALOG1 (analog input)
The input is the interface for differential analog signals between terminals X6/1, 2. It can be used as
a setpoint input or as an actual value input.
Inputs_ANALOG1
AIN1_nIn_a
C0400
AIN1_bError_b
1
2
C0034
X6
Fig. 2−9 Inputs_ANALOG1
System variables
Variable Data type Signal type Address Display
code
Display
format
Note
AIN1_nIn_a Integer Analog %IW11.0 C0400 dec [%] Analog input 1
AIN1_bError_b Bool Binary %IX11.1.0 − − Only when C0034 = 1:
TRUE if I < 2 mA
Selection of master voltage/master current
C0034 can be used to set whether the input is to be used for a master voltage or a master
current:
Code LCD
Possible settings
Info
Lenze Selection
C0034 Mst current 0 Selection: Master voltage/master
current
0 −10 V ... + 10 V (master voltage)
1 +4 mA ... +20 mA (master current)
2 −20 mA ... +20 mA
Please also observe the jumper position X3 at the front of the 9300 Servo PLC in this
connection (see terminal assignment).
Use as a 4 ... 20 mA master current input
If the input is used as a master current input (C0034 =1), then AIN1_bError_b = TRUE as long
as the absolute value of the master current is < 2 mA, otherwise it is FALSE.
C0598 can be used to set the response for the case that the absolute value of the master
current is < 2 mA:
Code LCD
Possible settings
Info
Lenze Selection
C0598 MONIT SD5 3 Monitoring configuration:
Absolute master current value across
X6/1, 2 < 2 mA
0 TRIP
2 Warning
3 Off