2.12 MCTRL_MotorControl (node number 131)
9300 Servo PLC
System blocks
2−82
L
9300 Servo PLC EN 5.1
2.12.17.6 LU − undervoltage monitoring
This function monitors the DC bus and protects the controller.
Error
Monitoring function System variable
Possible responses
No. Display TRIP Message Warning FAIL−QSP Off
x030 LU Undervoltage MCTRL_bUndervoltage_b
Lenze setting
Setting possible
The monitoring responds if the DC−bus voltage at the terminals +U
G
and −U
G
falls below a switch−off
threshold dependent on C0173 and it remains active until the corresponding switch−on threshold has
again been exceeded.
The DC−bus voltage is set under C0173 (^ 2−80).
The switch−off and switch−on thresholds dependent on C0173 can be gathered from the
following table:
Setting of C0173 Switch−off threshold Switch−on threshold
0 Mains < 400 V; with or without brake unit 285 V 430 V
1 Mains = 400 V; with or without brake unit 285 V 430 V
2 Mains = 460 V; with or without brake unit 328 V 473 V
3 Mains = 480 V; without brake unit 342 V 487 V
4 Mains = 480 V; with brake unit 342 V 487 V
The switch−off threshold defines the voltage level of the DC−bus voltage, at which the pulse
inhibit is activated.
Tip!
If the undervoltage lasts longer than 3 s or if the drive is powered up, this is entered into the fault
memory.
This can be the case if the control module is supplied externally via the terminals X5/39 and
X5/59 and the mains is switched off.
If the undervoltage has been eliminated (reconnection to the mains), the entry is not updated
in the fault memory but deleted because this is not an error but a controller status.
Undervoltages which last for less than 3 s are interpreted as a fault (e.g. power system fault) and
entered into the fault memory. In this case the fault memory is updated.