Technical data
General data and operating conditions
4 Technical data
4.1 General data and operating conditions
"Inverter Drives 8400" hardware manual
This manual contains data on the ambient conditions and the electromagnetic
compatibility (EMC) that also apply to the communication module.
Field Values
Order designation E84AYCIBV (coated version)
E84AYCIBS: (standard version)
Communication profile INTERBUS
Interfaces Input (IN): 9-pole Sub-D plug
Output (OUT): 9-pole Sub-D socket
Communication medium RS485
Network topology Ring
Type of node INTERBUS slave
Number of nodes 1 master
512 slaves
Baud rate 500 kbps or 2 Mbps
(can be set via DIP switch or code)
Max. cable length 400 m at 500 kbps
150 m at 2 Mbps
(between the individual INTERBUS nodes)
Process data words (PD) to be used 0 ... 10: 16 bits/word
(can be set via DIP switch or code)
Parameter data words (PCP) 0, 1, 2, 4: 16 bits/word
(can be set via DIP switch or code)
Max. number of data words 10 (PD + PCP): 16 bits/word
Max. PDU length 64 bytes
INTERBUS identification (module ID) 3 = 0x3 (PCP 0 words)
227 = 0xE3 (PCP 1 word)
224 = 0xE0 (PCP 2 words)
225 = 0xE1 (PCP 4 words)
Voltage supply External supply via the 2-pole plug connector
"+": U = 24 V DC (21.6 V - 0 % … 26.4 V + 0 %), I
max
= 180 mA
"-": Reference potential for external voltage supply
Conformities, approvals CE