E84AYCIB communication manual (INTERBUS)
Error messages
Possible causes and remedies
62 L EDS84AYCIB EN 4.0 - 11/2010
Invalid module configuration [0x01bc6430]
Invalid configuration [0x01bc8125]
Communication stack reset [0x01bc8126]
Invalid initialisation [0x01bc8127]
Data exchange stopped [0x01bc8131]
Response (Lenze setting in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Module configuration is faulty. Check and correct module configuration.
Response (Lenze setting in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked : Warning Information
Cause Remedy
The active configuration is invalid:
Data word sum (PD + PCP) > 10 words
Data word sum (PD + PCP) = 0
Adapt the number of PD and PCP:
Data word sum (PD + PCP) = 1 ... 10 words
Response (Lenze setting in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Error during processing the INTERBUS services Execute reinitialisation by the master.
Response (Lenze setting in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked : Warning Information
Cause Remedy
The INTERBUS initialisation has failed. Execute reinitialisation by the master.
Response (Lenze setting in bold) Setting: C13880/1
: None System fault : Fault Trouble : Quick stop by trouble : Warning locked Warning : Information
Cause Remedy
The data exchange at the INTERBUS has been
terminated.
Check cables and connections.
Execute reinitialisation by the master.