E84AYCIB communication manual (INTERBUS)
Monitoring
10 Monitoring
Communication fault
If INTERBUS communication is interrupted, e.g. due to cable break or INTERBUS master
failure, no process data are transmitted to the slave in the
"IBS-ACTIVE
" ( 57) status.
After the time to be parameterised by the user in C13881
has elapsed, the response
parameterised in C13880/1
is executed in the controller.
Settings in the »Engineer«
Under the Settings tab in the »Engineer« you can set the following parameters:
Reaction on interrupted INTERBUS communication (C13880/1
)
Delete process data (C13885
)
Setting of the process data which the controller is to process further for maintaining
internal communication when the INTERBUS has failed.
Monitoring time for INTERBUS communication failure (C13881)