EDS84AYCIB EN 4.0 - 11/2010 L 35
E84AYCIB communication manual (INTERBUS)
Commissioning
Possible settings through DIP switch
6.2.1 Setting the number of process data words (PD)
The number of process data words (PD) can be set via switches 1 ... 4 or code C13893
(for this, see Settings in the »Engineer«
( 38)).
0 ... 10 process data words can be used.
The current setting is displayed in C13860/2
.
Note!
The data word sum (PD + PCP) must amount to 1 ... 10 words. Impermissible
settings are reported by the LED "BE" (red blinking).
LED status displays
( 54)
The communication module then continues to operate internally with the
following values:
•PD = 2 (words)
•PCP = 1 (word)
DIP switch Number of
PD
Switch Max. number
of PCP
1 2 3 4
0 OFF OFF OFF OFF 4
1 OFF OFF OFF ON
2OFFOFFON OFF
3OFFOFFON ON
4OFFON OFF OFF
5OFFON OFF ON
6OFFON ON OFF
7OFFON ON ON 2
8 ON OFF OFF OFF
9 ON OFF OFF ON 1
10 ON OFF ON OFF 0
12345678
ON
OFF