E84AYCIB communication manual (INTERBUS)
Commissioning
Possible settings through DIP switch
36 L EDS84AYCIB EN 4.0 - 11/2010
6.2.2 Setting the number of parameter data words (PCP)
The number of parameter data words (PCP) can be set via switches 5 and 6 or code
C13892
(for this, see Settings in the »Engineer« ( 38)).
0, 1, 2 or 4 parameter data words can be used.
The current setting is displayed in C13860/1
.
Note!
The data word sum (PD + PCP) must amount to 1 ... 10 words. Impermissible
settings are reported by the LED "BE" (red blinking).
LED status displays
( 54)
The communication module then continues to operate internally with the
following values:
•PD = 2 (words)
•PCP = 1 (word)
DIP switch Number of PCP Switch Max. number of
PD
ID code
[hex]
5 6
0OFFOFF100x03
1OFFON 90xE3
2 ON OFF 8 0xE0
4 ON ON 60xE1
12345678
ON
OFF