E84AYCIB communication manual (INTERBUS)
Diagnostics
LED status displays
56 L EDS84AYCIB EN 4.0 - 11/2010
11.1.2 Fieldbus status displays
The LEDs BS and BE display the fieldbus status.
E84YCIB006
LED Colour Status Description
BS Green Off The communication module is not active on the fieldbus.
Data cycles are not executed.
Blinking
Communication has been established via the communication
module. The INTERBUS is active. Data cycles are executed.
BE Red On
INTERBUS communication is interrupted.
Data cycles are not executed.
Blinking
Impermissible setting:
Data word sum (PD + PCP) > 10
Data word sum (PD + PCP) = 0
The communication module has been initialised and continues to
operate internally with the following values:
PD = 2 (words)
PCP = 1 (word)
BE
BS
200 ms
200 ms
200 ms
200 ms