Seitenansicht 126
16×dig. I/O compact (single−wire conductor)
5
The compact system
5.2
L
5.2−5
EDSPM−TXXX−9.0−11/2009
DI 8xDC24V DIO/DO 4/4xDC24V 1A
L+ L+
.0 .0
.1 .1
.2 .2
.3 .3
.4 .4
.5 .5
.6 .6
.7 .7
FF
11
22
33
44
55
66
77
88
99
10 10
L
PW
ER
RD
BA
ADR.
0
1
+
PE
X1
DC
24V
DI 8xDC24V
DIO 4xDC24V 1A
DO 4xDC24V 1A
X3 X4
EPM-T831 1A.10
0213
epm−t051
Fig. 5.2−4 Front view of 16×dig. I/O compact (single−wire conductor)

Status display for digital inputs / outputs at the terminal strips X3 and X4
L+ LED (yellow) is lit when the supply voltage is applied.
.0 ... .7 LED (green) is lit when the output is triggered and/or a HIGH
level is detected at the input
F LED (red) is lit in case of overload, overheating, short−circuit
errors.
Terminal strip X3 assignment
X3/1 Not assigned
X3/2 ... X3/9 Digital inputs E.0 ... E.7
X3/10 GND (reference potential)
Terminal strip X4 assignment
X4/1 DC 24 V supply voltage
X4/2 ... X4/5 Digital inputs/outputs E/A.0 ... E/A.3
X4/6 ... X4/9 Digital outputs A.4 ... A.7
X4/10 GND (reference potential)