CAN GatewayECO
4
The modular system
4.2
L
4.2−1
EDSPM−TXXX−9.0−11/2009
4.2 CAN GatewayECO
The CAN GatewayECO is the interface between the process level and the master
bus system. The control signals at the process level are transmitted by the
electronic modules. These modules are connected with the CAN Gateway via the
backplane bus (EPM−T9XX). CAN Gateway and the connected electronic modules
communicate via the backplane bus. A configuration is not required.
l Up to 8 modules can be connected to a CAN Gateway
l Integrated power supply unit for the internal voltage supply and the voltage
supply of the connected electronic modules
– Power supply unit is fed via an external DC voltage source
l Only supports the electronic module types EPM−T2xx and EPM−T3xx
l Connection to the system bus (CAN) / CANopen via a 9−pole Sub−D plug
l Address and baud rate setting via DIP switch
l The baud rate is stored permanently in an EEPROM in the module
l LED for status display
PW
ER
R
D
B
A
D
C
24V
+
-
1
2
X1
EPM – T111 xx.xx
0
1
2
3
A
D
R.
64
32
16
8
4
2
1
L/C
1
0
epm−t225
Fig. 4.2−1 Overview of Can GatewayECO
Coding switch to set address and baud rate
LED for status display
9−pin Sub−D plug for the connection to the fieldbus
External voltage supply connection
View Pin Assignment Explanation
1
2
3
4
5
6
7
8
9
1 Not assigned −
2 CAN−LOW Data line
3 CAN−GND Data ground
4 Not assigned −
5 Not assigned −
6 Not assigned −
7 CAN−HIGH Data line
8 Not assigned −
epm−t023
9 Not assigned −
Description