8×digital input / output
4
The modular system
4.13
L
4.13−2
EDSPM−TXXX−9.0−11/2009
( Stop!
If the voltage supply (DC 5 V via the backplane bus) fails, the
module will malfunction:
l Switched outputs carry voltage if one input is assigned with a
HIGH level,
l The module can be destroyed since the outputs are no longer
resistant to short circuits.
The emergency−off switch ensures that when being operated, the
outputs do not carry any voltage and the inputs are not assigned
with a HIGH level.
DIO 8xDC24V 1A
.0
L+
.1
.2
.3
.4
.5
.6
.7
F
1
2
3
4
5
6
7
8
9
L
10
EPM – T230 1A
1
2
0
3
–
+
2
1
3
4
5
6
7
8
9
10
.
Z
Z
Z
Z
DC 24 V
(DC +18 … +35 V)
epm−t027 epm−t028
Fig. 4.13−2 Front view and connection of 8×digital input / output
Status display L+; LED (yellow) is lit
when a supply voltage is applied
Terminal strip assignment
details
1 DC 24 V supply voltage
2 Digital input / output E/A.0
Status display .0 ... .7; LED (green) is
lit when the corresponding output is
triggered
3 Digital input / output E/A.1
4 Digital input / output E/A.2
5 Digital input / output E/A.3
Status display F; LED (red) is lit in
case of overload, overheating or
short circuit
6 Digital input / output E/A.4
7 Digital input / output E/A.5
8 Digital input / output E/A.6
9 Digital input / output E/A.7
10 GND (reference potential)
Connection to backplane bus
Emergency−off switch
Z
Load
Status display and terminal
assignment
Kommentare zu diesen Handbüchern