Index table
15
Appendix
15.1
L
15.1−10
EDSPM−TXXX−9.0−11/2009
Index ImportantPossible settingsName
SelectionLenze
I2360
h
*
Property function
forcing
0
0 {1} 1 · Forcing of digital outputs (I6200
h
) and
analog outputs (I6411
h
)
· After a restart, I2360
h
is set 0
0 Forcing deactive in "Pre−Operational" state Forcing only possible in "Operational" state
1 Forcing active in "Pre−Operational" state Forcing only possible in "Pre−Operational"
state
I2361
h
CAN mode 0
0 {1} 1
Display only
Active communication mode
0 Lenze system bus mode
1 CANopenmode
I2400
h
¿
Timer value 0 {1 ms} 65535
Monitoring time for process data input
objects
For the compact system, only index I2400
h
,
subindex 1 is available
8.9−1
1 PD01 0
2 PD02 0
3 PD03 0
4 PD04 0
5 PD05 0
6 PD06 0
7 PD07 0
8 PD08 0
9 PD09 0
10 PD10 0
I2410
h
*
Time−out short
circuit monitoring
2 0 {1 ms} 65535 Only available for the compact system.
If a digital output has a short circuit and
the time set has been exceeded, the
module switches to the status set in
I1029
h
, subindex 2.
I2500
h
Dummy object for
PDO mapping
Display only
Index is only available in the compact
system
I3001
h
¿
Config
analog/counter
module 1
00000000
h
{1
h
} FFFFFFFF
h
Configuration of analog module,
2/4xcounter module, SSI interface module
or 1xcounter/16xdigital input module on
slot 1
· I3001
h
can only be accessed via Global
Drive Control (GDC). Use I3401
h
in
CoDeSys programming systems.
· I3001
h
is only available for the modular
system.
12.3−1
12.4−1
12.5−1
12.6−1
1 0
h
2 0
h
3 0
h
4 0
h
I3002
h
¿
Config
analog/counter
module 2
00000000
h
{1
h
} FFFFFFFF
h
Configuration of analog module,
2/4xcounter module, SSI interface module
or 1xcounter/16xdigital input module on
slot 2
· I3002
h
can only be accessed via Global
Drive Control (GDC). Use I3401
h
in
CoDeSys programming systems.
· I3002
h
is only available for the modular
system.
12.3−1
12.4−1
12.5−1
12.6−1
1 0
h
2 0
h
3 0
h
4 0
h
I3003
h
¿
Config
analog/counter
module 3
00000000
h
{1
h
} FFFFFFFF
h
Configuration of analog module,
2/4xcounter module, SSI interface module
or 1xcounter/16xdigital input module on
slot 3
· I3003
h
can only be accessed via Global
Drive Control (GDC). Use I3401
h
in
CoDeSys programming systems.
· I3003
h
is only available for the modular
system.
12.3−1
12.4−1
12.5−1
12.6−1
1 0
h
2 0
h
3 0
h
4 0
h