Lenze EPM−T9XX Modular system Bedienungsanleitung Seite 229

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 544
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 228
Transmitting process data
Indices for setting the process data transmission
9
Network via CANopen
9.3
9.3.9
L
9.3−13
EDSPM−TXXX−9.0−11/2009
Process data objects for output data
Index
Name Possible settings Important
Lenze Selection
I1800
h
¿
9.3−3
1 COB−ID used by
TxPDO 1
767 385 {1} 2047 Defining the individual identifiers for
process data object 1
2
Transmisson type 255 0 {1} 255 Defining the transmission mode
0 Function deactivated The output data are accepted on sync
telegram transmission.
1 ... 240 Process data transfer after sync no. 1
...
Process data transfer after sync no. 240
The output data are accepted after
transmission of the set number (1 ... 240)
of sync telegrams.
254 Time−controlled process data transfer Only if a cycle time is set in I180x
h
,
subindex 5
255 Event−controlled process data transfer
255 Event−controlled process data transfer with cyclic
overlay
Only if a cycle time is set in I180x
h
,
subindex 5
3 Inhibit time 0 0 {1 ms} 65535 Inhibit time
5 Event time 0 {1 ms} 65535 Cycle time
... ...
I1809
h
¿
Index is only available in the modular
system
9.3−3
1 COB−ID used by
TxPDO 10
1984 385 {1} 2047 Defining the individual identifiers for
process data object 10
2
Transmisson type 255 0 {1} 255 Defining the transmission mode
0 Function deactivated The output data are accepted on sync
telegram transmission.
1 ... 240 Process data transfer after sync no. 1
...
Process data transfer after sync no. 240
The output data are accepted after
transmission of the set number (1 ... 240)
of sync telegrams.
254 Time−controlled process data transfer Only if a cycle time is set in I180x
h
,
subindex 5
255 Event−controlled process data transfer
255 Event−controlled process data transfer with cyclic
overlay
Only if a cycle time is set in I180x
h
,
subindex 5
3 Inhibit time 0 0 {1 ms} 65535 Inhibit time
5 Event time 0 0 {1 ms} 65535 Cycle time
Seitenansicht 228
1 2 ... 224 225 226 227 228 229 230 231 232 233 234 ... 543 544

Kommentare zu diesen Handbüchern

Keine Kommentare