5 Commissioning the controller
5.7 Error messages (backplane bus)
43
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.7 Error messages (backplane bus)
Error messages are represented on the Diagnostics tab of the I/O module coupler.
[5-5] Example: Topology error, the EPM-S501 module cannot be reached at the backplane bus.
Error messages
The following error messages can be displayed:
Error number Error text/remedy
11 Too many I/O modules for the task cycle time selected.
• Increase cycle time.
12 FIFO response full.
• Contact Lenze
32 Timeout reset
• Contact Lenze
33 Timeout reset error
• Contact Lenze
96 Too many I/O modules for the task cycle time selected.
• Increase cycle time.
97 Too many I/O modules for the task cycle time selected.
• Increase cycle time.
98 Too many I/O modules for the task cycle time selected.
• Increase cycle time.
99 Too many I/O modules for the task cycle time selected.
• Increase cycle time.
100 Too many I/O modules for the task cycle time selected.
• Increase cycle time.
101 Timeout for master queue operation
• Contact Lenze
102 Bus initialisation error with one I/O module
• Contact Lenze
103 Master queue operation error
• Not all I/O modules can be reached.
104 Read semaphore timeout for group 1
105 Read semaphore timeout for group 2
106 Read semaphore timeout for group 3
107 Write semaphore timeout for group 1
108 Write semaphore timeout for group 2
109 Write semaphore timeout for group 3
110 Internal error of the backplane bus hardware
• Contact Lenze
116 Read semaphore timeout for group 1
Kommentare zu diesen Handbüchern