Lenze c300 Bedienungsanleitung Seite 80

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 195
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 79
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17 80
11 Remote maintenance and diagnostics
11.1 Status LEDs of the Controllers
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.1 Status LEDs of the Controllers
The Controllers are provided with LEDs which indicate the current operating status. Depending on
the Controller used, the colours of the LEDs vary.
[11-1] Example: Cabinet Controller 3200 C
Power: green/blue*, yellow
Error: green, red
Status 1: green, yellow
Status 2: no function
* Device-dependent LED colour: Either green or blue
LED
Colour 1 / colour 2
Interval Meaning
Power
green/blue* Constant Startup completed successfully.
No error pending
Controller is switched on
Supply voltage OK
Yellow Constant The supply voltage has fallen below the minimum value. Voltage
buffering by external UPS (optional, for Controller 3241 C) ( 158)
UPS functionality of the controllers
( 68)
blinking
(2.0 Hz)
Status after switch-on/restart
(For Controller c300/p300 in preparation.)
green/
blue*
Yellow blinking
(0.5 Hz)
"System clock is not synchronised" (time information missing).
Note:
If the Controller is switched off for more than two weeks, the time
information set will be lost.
• The next starting process creates a logbook entry (power LED is
blinking green/blue).
The current time can be set manually via »WebConfig«
(parameter 91).
Only for Controller 3241 C: Battery pack (ACCU-PACK) is not fully charged.
The length of the dark phase indicates the charge status:
Battery pack almost empty: Long dark phase
Battery pack almost full: Short dark phase
green blinking
(5.0 Hz)
Only for Controller 3241 C: Error status of the battery pack (ACCU-PACK)
UPS function is not available, possible cause:
Connection to the battery pack interrupted
Battery pack not connected, cable break/short circuit
green Yellow blinking
(5.0 Hz)
Error
red blinking
(5.0 Hz)
Error
Fatal error (abort)
SD card not available/not inserted correctly
No operating system licence available
green red blinking
(5.0 Hz)
Mains switching required
Status 1 ("busy")
Seitenansicht 79
1 2 ... 75 76 77 78 79 80 81 82 83 84 85 ... 194 195

Kommentare zu diesen Handbüchern

Keine Kommentare