7 Programming with the »PLC Designer«
7.5 Creating remanent variables (retain/persistent)
65
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.5.1 Storage of retain data on the SD card (only Controllers 3221 C/3231 C)
For Controllers 3221 C/3231 C, the values of the RETAIN variables are by default saved to the device
only.
•Use the L_Util_Retain function (from the L_Util.lib library) to save the RETAIN values to the SD
card of the controllers. Like this, the retain data can then be re-used, for instance after a device
replacement.
RETAIN values saved to the SD card offer the benefit of subsequent use of these values after a
device replacement (subsequent use of the SD card).
L_Util_Retain
[7-1] Program example: Use of the L_Util_Retain function
When being called, the L_Util_Retain function saves the retain/persistent variables to the SD card
to file: retains.ret (directory: IPC\PLC).
Note!
The SD card is only suitable for storing retain data if the RETAIN values do not change
very often.
It is not possible to save the RETAIN values to the SD card during every PLC cycle.
SD cards only have a limited number of write/read cycles. Thus, the retain variables
should not be saved at very short time intervals.
Please avoid calling the L_Util_Retain() function in a motion task. The creation of the
RETAIN file prolongs the current PLC cycle of the calling task by several 100 ms.
•The functions SysSaveRetains() and SysRestoreRetains() provided in the
SysPlcCtrl23.Library are not supported and must not be used.
Function Library Function
L_Util_Retain() L_Util.library Save retain data to the SD card of the
controller.
PROGRAM PLC_PRG
VAR
FB_LUtilRetain: L_Util_Retain;
xRetainsIntoFile_LUtilRetain: BOOL;
instSetRetainValues: SetRetainValues;
xSetRetain: BOOL;
xStoreRetains_LUtilRetain: BOOL;
END_VAR
Note!
Device replacement: Avoiding the loss of retain data
The L_Util_Retain function is only required for the Controllers 3221 C/3231 C.
•Use the L_Util_Retain function in the desired application in order to be able to re-use
the retain data, if required.
In the event of a device replacement, the L_Util_Retain function must already have
been used in the application before, since otherwise the retain data are deleted.