Error messages
CAN generator
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Error during reading of the NMT master settings [NWCAN0010]
12.3.3 Synchronisation
SYNC master not defined [NWCAN0011]
SYNC transmission identifier {0} is not supported by node [NWCAN0012]
SYNC transmission cycle time {0} ms is not supported by node [NWCAN0013]
SYNC reception identifier {0} is not supported by the nodes [NWCAN0014]
Response (Lenze setting printed in bold)
Error Warning Information
Cause Remedy
The access to the NMT master settings has failed.
Response (Lenze setting printed in bold)
Error Warning Information
Cause Remedy
In the specified network either process data objects or
processes (tasks) are connected to the synchronisation
object. However, no synchronisation object generator is
defined.
• Change to the Synchronisation tab of the network
specified.
•Under SYNC source, select the node the
synchronisation object is to send cyclically.
Response (Lenze setting printed in bold)
Error Warning Information
Cause Remedy
The indicated SYNC source does not support the
indicated COB-ID.
Select a COB-ID under SYNC source in the
Synchronisation tab of the network specified which
supports all nodes. (E. g: 128).
Response (Lenze setting printed in bold)
Error Warning Information
Cause Remedy
The indicated SYNC source does not support the
specified cycle time for sending the synchronisation
object.
Select a cycle time under SYNC source in the
Synchronisation tab of the network specified which
supports all nodes.
Response (Lenze setting printed in bold)
Error Warning Information
Cause Remedy
The SYNC receiver specified does not support the defined
COB-ID.
Select a COB-ID under SYNC source in the
Synchronisation tab of the network specified which
supports all nodes. (E. g: 128).