Electrical installation
EMC−compliant wiring
6
29
Lenze ¯ BA_3241C ¯ 4.0
6.2 EMC−compliant wiring
Notes on EMC−compliant wiring
General notes ¯ The electromagnetic compatibility of the system depends on the type of installation
and care taken. Especially consider the following:
Structure
Shielding
Earthing
¯ For installations differing from the one described, the evaluation of the conformity
with the EMC Directive requires a check of the system regarding the EMC limit
values. This for instance applies to:
Use of unshielded cables
¯ The compliance with the EMC Directive is in the responsibility of the user.
If you observe the following measures, you can assume that no EMC problems will
occur during operation and that compliance with the EMC Directive and the EMC
law is achieved.
If devices which do not comply with the CE requirement concerning noise
immunity (EN 6100042) are operated close to the system, these devices may be
electromagnetically affected by the system.
Structure ¯ Provide electrical contact between the DIN rail and the earthed mounting plate:
Mounting plates with electrically conductive surfaces (zinccoated or stainless steel)
allow permanent contact.
Painted plates are not suitable for an EMCcompliant installation.
¯ If you use several mounting plates:
Connect as much surface of the mounting plates as possible (e.g. with copper
strips).
¯ When laying the cables, pay attention to the separation of signal cables and mains
cables.
¯ Lay the cables as close as possible to the reference potential. Freely suspended cables
act like aerials.
Shielding ¯ Only use cables with braided shield if possible.
¯ The overlap rate of the shield should be higher than 80%.
¯ For data cables for serial connection, always use metal or metallised connectors.
Connect the shield of the data cable to the connector shell.
Earthing ¯ Earth all metallically conductive components using suitable cables connected to a
central earthing point (PE bar).
¯ Keep to the minimum crosssections defined in the safety instructions:
For EMC not the cable crosssection is important, but the surface of the cable and
the contact with a crosssection as large as possible, i.e. large surface.