Lenze EMF2113IB Bedienungsanleitung Seite 40

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 119
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 39
Installation
Electrical installation
7
Feldbus-Baugruppe 2113 INTERBUS
7.4
7.4.3
L
7.4-5
EDSIBS-1.0-06/2003
Electrical connection Plug connector with threaded terminal end
Possible connections
rigid: 1.5 mm
2
(AWG 16)
flexible:
without wire crimp cap
1.5 mm
2
(AWG 16)
with wire crimp cap, without plastic sleeve
1.5 mm
2
(AWG 16)
with wire crimp cap, with plastic sleeve
1.5 mm
2
(AWG 16)
Tightening torque 0.5 ... 0.6 Nm (4.4 ... 5.3 lb-in)
Bare end 6mm
)
))
) Note!
Basic devices with extended AIF interface opening (8200 vector
front) can be internally supplied. The part of the drawing
highlighted in grey shows the jumper position.
l In the delivery state of the frequency inverter these are not
internally supplied.
l For internal voltage supply, put the jumper in the position
indicated below.
Lenze setting
only external voltage supply
Internal voltage supply
Connection terminals 28
Internal DC voltage supply 29
Show/Hide Bookmarks
Seitenansicht 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 118 119

Kommentare zu diesen Handbüchern

Keine Kommentare