7.5.9 Special features when using 82XX, 8200 vector and 93XX
}
}}
} Danger!
Please note
l For safe operation it is absolutely necessary to observe the
notes for the controllers given in this chapter.
l Please observe the corresponding Operating Instructions of the
controllers.
820X • Parameter setting (codes except process data) is only possible when the controller is inhibited
(DRIVECOM controller status unequal ”OPERATION ENABLED“). Parameters are accepted when the
controller is enabled, but they are not saved.
• A TRIP must only be reset through INTERBUS:
If the controller is set to the status TRIP while being operated with INTERBUS control
(L-C0001 = 3) and if the TRIP is reset t hrough terminal 28, t he drive can start f or a short time.
When resetting a fault via INTERBUS, this does not occur.
• A f t er the command ”TRIP re set“ the 820X controller i s basically initialized. During this time the
controller does not accept any services.
• Always send the direction of rotation with a low setpoint before the new setpoint:
If the setpoint and the direction of rotation are changed at the same time via the DRIVECOM speed
setpoint, the speed can change to the wrong direction or rotation for a short time. This is because
the setpoint is sent to the controller as unipolar value before and the information about the
direction of rotation is sent.
8200 v ector • Digital and analog input and output signals can be freely configured (see Operating Instructions for
8200 vector; codes L-C0410, L- C0412, L-C0417 and L-C0421)
• A change of code L-C0001 to “3“ preconfigures the process data words in the cont ro ller.
93XX • Set the signal configuration L-C0005 = xxx3 instead of the operating mode L-C0001.
• The change of the code L-C0005 to xxx3 starts the preconfiguration of the process data words in
the controller
• Set t he parameter L-C0142 = 0 (auto start lo ck), to avoid a short time start of the drive during the
initialization pha se.