Data transfer
Process data signals of Lenze controllers
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
L
7.6-14
EDSIBS-1.0-06/2003
Control word AIF-CTRL for 8200 vector (Lenze code C0135, index 5F78
hex
)
AIF-CTRL.Bxx Default setting:
C0001=3 if C0007
≤ 51
Default setting:
C0001=3 if C0007 > 51
Adjustab le in L-C0410/..
00,
00 = C0046 active
01 = NSET1-JOG1 (C0037) a cti ve
1
01
10 = NSET1-JOG2 (C0038) a cti ve
11 = NSET1-JOG3 (C0039) a cti ve
Freely configurable by user
2
02 DCTRL1-CW/CCW 0=notactive
1=active
3
03 AIF-CTRL-QSP 0=notactive
1=active
AIF-CTRL-QSP 0=notactive
1=active
4
04 NSET1-RFG1-STOP 0=notactive
1=active
5
05 NSET1-RFG1-0 0=notactive
1=active
6
06 MPOT1-UP 0=notactive
1=active
Freely configurable by user
7
07 MPOT1-DOWN 0=notactive
1=active
8
08 Freely configurable by user 9
09 AIF-CTRL-CINH 0=notactive
1=active
AIF-CTRL-CINH 0=notactive
1=active
10
10 AIF-CTRL-TRIP-SET 0=notactive
1=active
AIF-CTRL-TRIP-SET 0=notactive
1=active
11
11 AIF-CTRL-TRIP-RESET 0 -> 1 = Edge from 0 to 1 AIF-CTRL-TRIP-RESET 0 -> 1 = Edge from 0 to 1 12
12 DCTRL1-PAR2/4 0=notactive
1=active
13
13 DCTRL1-PAR3/4 0=notactive
1=active
Freely configurable by user
14
14 MCTRL1-DCB 0=notactive
1=active
15
15 Freely configurable by user Freely configurable by user 16
AIF
AIF-IN
AIF-CTRL
AIF-IN.W2
AIF-IN.W1
.B15
.B12
.B0
.B1
.B2
.B3
.B4
...
...
...
...
...
...
...
...
...
...
...
...
.B8
.B9
.B10
.B11
DCTRL
QSP
CINH
TRIP-SET
TRIP-RESET
DCTRL
16 bits
16 bits
16 bits
2141LON011_en
Fig. 7.6-4 Function block AIF-IN in 8200 vector (freely programmable assignment)