Data transfer
Process data channel configuration
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.1
L
7.6-3
EDSIBS-1.0-06/2003
7.6.1.2 Setpoint source selection
The setpoint source selection for these controllers is determined under code
L-C0001 (5FFE
hex
). An evaluation of process data is only possible if code L-C0001
is set to 3 when the controller is operated togetherwith thefieldbus module.The
process data channel which describes the frequency setpoint (L-C0046) and the
control word (parameter channel, L-C0135) is the setpoint source
.
)
))
) Note!
Please ensure that the setpoint source (L-C0001) is the same for
all parameter sets used.
The setpoint source selection for these controllers is determined under code
L-C0001 (5FFE
hex
). An evaluation of process data is only possible if code L-C0001
is set to 3 when the controller is operated togetherwith thefieldbus module.The
process data channel which describes the frequency setpoint (L-C0046) and the
control word (parameter channel, L-C0135) is the setpoint source
.
Check in L-C0412/x whether the assignment of setpoint source and analog signal
is correct and change, if necessary.
)
))
) Note!
Please ensure that the setpoint source selection (L-C0001) is the
same for all parameter sets used.
The value in code C0005 must be set to xxx3 for bus operation (x = selected
preconfiguration).
Communication requires that AIF-IN 1 ... 3 or AIF-OUT 1 ... 3 and if available
the
AIF management are part of the control configuration of the IEC61131 project.
82XX controllers
Controller 8200 vector
93XX controllers
Servo PLC 9300 / Drive PLC