9 Mains and environment
9.2 Ambient conditions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
For motors without a gearbox the following correction values k
ϑ
result:
9.2.2 Max. ambient temperature, inverter
DSD considers the drive-specific reduction factors and an ambient temperature range of 0 ... 60 °C.
• The ranges from -20 ... 0 °C have to be checked manually.
• In a temperature range of 0 ... 40 °C, operation of the components can be carried out without a
power derating.
• For inverters the derating factor is stored in the DSD device-specifically.
ϑ
opr
k
ϑ
0 ... 40 °C 1
≤ 45 °C 0.95
≤ 50 °C 0.9
≤ 55 °C 0.85
≤ 60 °C 0.8
Note!
• The DSD does not take sub-zero temperatures into consideration.
• For an ambient temperature < 0°C you enter 0°C.
• Make sure that the ambient conditions suit the motors. As a help, use the tables with
the correction values.
Note!
The upper and lower limit values can vary for the different inverters.
In the chapter "Inverters
" ( 346) the characteristics of the different inverter types are
listed.