Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17 108
11 Parameter reference
11.3 Parameters of the communication module for slot MXI2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14041
C14042
C14043
C14044
Parameter | Name:
C14041 | EPL version
Data type: UNSIGNED_8
Index: 10534 = 0x2926
EPL index: not available
The code describes the version of the POWERLINK communication profile implemented by the communication
module.
The higher-order nibble describes the major version, the lower order nibble describes the minor version. The
implemented value corresponds to the POWERLINK version 2.0.
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14042 | Current EPL device address
Data type: UNSIGNED_8
Index: 10533 = 0x2925
EPL index: 0x1F93.0x01
The code displays the currently valid EPL node address (Node ID).
• The node ID must be unequivocal in the EPL network segment.
• See also C14044
.
Display area (min. value | unit | max. value)
1 240
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14043 | EPL device address selection
Data type: UNSIGNED_8
Index: 10532 = 0x2924
EPL index: 0x1F93.0x02
The code indicates whether the EPL node address (node ID) has been set via DIP switches at the communication
module or via the software.
• 0: Node ID has been set via software (C14044
).
• 1: Node ID has been set via DIP switches at the communication module.
Node address setting
( 36)
Display area (min. value | unit | max. value)
0 1
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14044 | EPL device address SW
Data type: UNSIGNED_8
Index: 10531 = 0x2923
EPL index: 0x1F93.0x03
This code serves to set the EPL node address (node ID) via the software.
The value "0" (Lenze setting) is not a valid node ID. It serves to activate the setting via the DIP switches.
Node address setting
( 36)
Setting range (min. value | unit | max. value) Lenze setting
1 240 0
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT