10 Error messages
10.2 POWERLINK error messages
67
Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10.2 POWERLINK error messages
• The POWERLINK error messages are displayed via code C13910 / C14910.
• In order to distinguish between the error responses, the displayed error messages are preceded
with 3 characters:
Response Meaning
EL_... Trouble (Fault)
QL_... Quick stop by trouble
WL_... Warning locked
I__... Information (Info)
Error number Name Description
hex dec
0x1 1 EL_ LeaveData
Exchange
The POWERLINK data exchange has been completed (the node
recognises that it does not have the "DataExchange" status
anymore).
Causes & remedy:
• See error description
EPL: DataExchange exited [0x00c88131]
( 64)
Codes:
• C13883
/ C14883 (error response)
0x3 3 QL_ LeaveData
Exchange
0x4 4 WL_LeaveData
Exchange
0x6 6 I__LeaveData
Exchange
0x18263 98915 EL_EPL_BOOTUP_1 The Managing Node could not start the POWERLINK network.
OR:
Not all required nodes were found.
Causes & remedy:
• See error description
EPL MN: Network has not been started (bootup-1) [0x00c88263]
( 64)
Codes:
• C13891/2
/ C14891/2 (error response)
0x38263 229987 QL_EPL_BOOTUP_1
0x48263 295523 WL_EPL_BOOTUP_1
0x68263 426595 I__EPL_BOOTUP_1
0x18264 98916 EL_EPL_BOOTUP_2 The Managing Node could not transfer all nodes into the
"NMT_CS_OPERATIONAL" status via process data exchange.
Causes & remedy:
• see error description
EPL MN: Not all nodes are in the operational status (bootup-2)
[0x00c88264] ( 64)
Codes:
• C13891/2
/ C14891/2 (error response)
0x38264 229988 QL_EPL_BOOTUP_2
0x48264 295524 WL_EPL_BOOTUP_2
0x68264 426596 I__EPL_BOOTUP_2
0x18265 98917 EL_EPL_CN_SYNC_
LOSS
In the Controlled Node, the synchronisation cycle of the Managing
Node has failed. The Controlled Node automatically changes to the
"NMT_xx_PREOPERATIONAL_1" status and waits for a new run-up
by the Managing Node.
Causes & remedy:
• see error description
EPL: Synchronisation lost from MN [0x00c88265]
( 65)
Codes:
• C13127/3
/ C14127/3 (monitoring threshold)
• C13891/3
/ C14891/3 (error response)
• C13127/1
/ C14127/1 (error counter)
0x38265 229989 QL_EPL_CN_SYNC_
LOSS
0x48265 295525 WL_EPL_CN_SYNC_
LOSS
0x68265 426597 I__EPL_CN_SYNC_
LOSS