Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 473
11 Basic drive functions
11.6 Homing
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.6.5.3 Resetting home position
By setting the control input HM_bResetHomePos to TRUE, the "Home position known" status can be
reset.
• The status outputs HM_bDone and HM_bHomePosAvailable are reset to FALSE.
Note!
For the encoderless motor control types (from software version V3.0) the following
applies:
If V/f control or sensorless vector control has been selected, this function is only effective
if the position controller has also been selected for the position control
(C02570
= "2: position controller active").
For the encoderless motor control types (from software version V5.0) the following
applies:
If the V/f control or sensorless vector control is selected, this function can be activated
irrespective of the use of the position controller.