Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 825
14 Parameter reference
14.2 Parameter list | C00958
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00958
C00959
C00960
C00961
C00962
Parameter | Name:
C00958 | VFC: VVC gain
Data type: UNSIGNED_32
Index: 23617
d
= 5C41
h
From software version V3.0
V/f control
Setting range (min. value | unit | max. value) Lenze setting
0.00 V/A 750.00 0.00 V/A
Read access Write access CINH PLC STOP No transfer Scaling factor: 100
Parameter | Name:
C00959 | VFC: VVC reset time
Data type: UNSIGNED_32
Index: 23616
d
= 5C40
h
From software version V3.0
V/f control
Setting range (min. value | unit | max. value) Lenze setting
0.01 ms 2000.00 2000.00 ms
Read access Write access CINH PLC STOP No transfer Scaling factor: 100
Parameter | Name:
C00960 | VFC: V/f voltage boost
Data type: INTEGER_32
Index: 23615
d
= 5C3F
h
From software version V3.0
V/f control
Setting range (min. value | unit | max. value) Lenze setting
0 V 1000 0V
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00961 | VFC: Load - cw/ccw-operation
Data type: UNSIGNED_32
Index: 23614
d
= 5C3E
h
From software version V3.0
V/f control
Selection list (Lenze setting printed in bold)
0 CW: mot. / CCW: mot.
1 CW: mot. / CCW: regen.
2 CW: regen. / CCW: mot.
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00962 | VFC: Load adjustment
Data type: UNSIGNED_32
Index: 23613
d
= 5C3D
h
From software version V3.0
V/f control
Setting range (min. value | unit | max. value) Lenze setting
0.00 % 200.00 20.00 %
Read access Write access CINH PLC STOP No transfer Scaling factor: 100