Lenze EVS9332xP Bedienungsanleitung Seite 124

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 445
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 123
Wiring of the standard device
Standard devices with a power of 45 kW
Motor connection
5
5.6
5.6.6
5.6−8
EDSVS9332P EN 5.0−07/2013
Characteristics of the connection for motor temperature monitoring:
Terminals T1, T2
Connection
l PTC thermistor
PTC thermistor with defined tripping temperature (acc. to
DIN 44081 and DIN 44082)
l Thermal contact (NC contact)
Thermostat as NC contact
Tripping point l Fixed (depending on the PTC/thermal contact)
l PTC: RJ
> 1600 W
l Configurable as warning or error (TRIP)
Notes l Monitoring is not active in the Lenze setting.
l If you do not use a Lenze motor, we recommend the use of a PTC
thermistor up to 150°C.
T1
T2
PE
U
VW
2
3
0
4
T1
T2
2.5 Nm
22.1 lb-in
U, V, W,
PE
M8
15 Nm
132 lb-in
1
M5x12
3 Nm (26.5 lb-in)
}
+
PE
9300std031
Fig. 5.6−4 Motor connection with PTC thermistor or thermal contact (NC contact)
PE stud
PE cable connection with ring cable lug
U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable.
Max. connectable cable cross−section: 120 mm
2
with ring cable lug
Shield clamps
Place shields of motor cable with large surface on the shield sheet and
fasten with shield clamps and M5 × 12 mm screws
Cable ties
Strain relief of motor cable
T1, T2 for motor temperature monitoring
Cable connection for PTC thermistors or thermal contacts (NC contacts)
Place shield with large surface on PE stud
Seitenansicht 123
1 2 ... 119 120 121 122 123 124 125 126 127 128 129 ... 444 445

Kommentare zu diesen Handbüchern

Keine Kommentare