Commissioning
Automatic control parameter identification
Important notes
6
6.15
6.15.1
6.15−1
EDSVS9332P EN 5.0−07/2013
6.15 Automatic control parameter identification
6.15.1 Important notes
Stop!
ƒ A control parameter identification can only be carried out if
the drive is not exposed to external torques. In the event of
overhauling loads, for instance, a motion must not be
activated through the function.
ƒ Release the brake (if mounted) before executing the control
parameter identification.
ƒ In order to comply with the number of revolutions, a brake
resistor or a regenerative power supply unit and a constant
moment of inertia are required.
– A major change to the Lenze setting in the "Limitation" field
(C1182  C1185) may cause deviations during the
identification of the distance parameters and thus can cause
deviations with regard to the controller setting.
ƒ The motion to be carried out by the control parameter
identification must be set in a way that even the slowest
rotating element of the drive train is still moving significantly.
ƒ The controller has to be inhibited (X5/28 = LOW).
ƒ The drive has to be at standstill.
Note!
If the requirements are not met, the control parameter
identification is not executed and an error code is set.
( 6.15−4)
ƒ In the case of a reactivation, the error is reset and the function
is initialised.
6.15.2 Description
How to open the dialog box (device description, from version 8.0):
1. Open the "short setup" menu.
2. Double−click the "DIALOG control parameter identification".
Requirements for the
activation