Wiring of the standard device
Control terminals
Device variant with "Safe torque off" function
5
5.8
5.8.4
5.8−6
EDSVS9332P EN 5.0−07/2013
Internal voltage supply
ƒ If a freely assignable digital output (e. g. X5/A1) is fixedly applied to
HIGH level, it serves as an internal voltage source. An output can be
loaded with a maximum of 50 mA.
– Via a digital output you can supply the relay K
SR
and two digital
inputs (X5/28, and for instance X5/E1) with voltage.
– For the maximum connection (relay K
SR
and X5/E1 ... X5/E5) you have
to connect two digital outputs in parallel and fixedly apply them to
HIGH level.
ƒ For the supply of the analog inputs (X6/1, X6/2 and X6/3, X6/4) you
have to set a freely assignable analog output (e. g. X6/63) permanently
to HIGH level.
GND2 +24V+5 V
DIGOUT4
E5
A2 A3 A4 ST1
ST2
59
39
3k
47k
50mA
50mA
50mA
50mA
X5
28
E1 E2 E3 E4
3k
3k
3k
3k
3k
X11
K31K32 33 34
S1 S2
IN1 IN2
IN3
IN4
+
K
SR
A1
Z1
X3
GND1 GND1
X6
12
3
4
7762
63
242R
1
2
3
4
5
6
100k
100k
100k
100k
3.3nF
AIN1 AIN2
AOUTx
AOUT2
AOUT1
1
3
247
10k 10k
9300vec135
Fig. 5.8−5 Wiring of digital and analog inputs/outputs with active "Safe torque off" function
and internal voltage source
S1 Deactivate pulse inhibit (1st disconnecting path)
S2 Enable controller (2nd disconnecting path)
Z1 Programmable logic controller (PLC)
The PLC monitors the ˜Safe torque off˜ function
X5/A4 Feedback via a digital output (e. g. DIGOUT4)
NO contact or NC contact
Z
Load
Minimum wiring required for operation
Terminal assignment in the Lenze setting: 5.8−9
Note!
If you load a basic configuration C0005 = xx1x (e.g. 1010 for
speed control with control via terminals), the following terminals
are switched to a fixed signal level:
ƒ Terminal X5/A1 to FIXED1 (corresponds to DC 24 V).
ƒ Terminal X6/63 to FIXED100% (corresponds to 10 V).